3-Phase AC Generator

DESCRIPTION

Genset Technical Data

Genset Model KT-110/S

Prime power (kVA/kW) 100 / 80

Standby power (kVA/kW) 110 / 88

Output frequency (Hz) 50

Rated speed (RPM) 1500

Rated voltage (V) 400

Rated current (A) 144.3

Phase 3

Fuel consumption of 75% load (L/hr) 17

Fuel consumption of 100% load (L/hr) 22

Noise level dB(A) @7m 68.9

Fuel tank capacity (L) 200

Dimension  (LxWxH) (mm) 2700*1100*1450

Weight (kg) 1900

Engine model KT6BT5.9-G2

Alternator model KT274C

Voltage regulation rate ≤±1%

Random voltage variation ≤±1%

Frequency regulation rate ≤±5%

Random frequency variation ≤±0.5%

Engine Specifications

Engine model KT6BT5.9-G2

Engine manufacturer KATE POWER

Number of cylinders 6

Cylinder arrangement Vertical in-line

Cycle 4 stroke

Aspiration Turbocharged

Bore x Stroke (mm x mm) 102 x 120

Displacement (Liter) 5.9

Compression Ratio 17.3:1

Prime power/speed (kW/RPM) 86/1500

Standby power/speed (kW/RPM) 92/1500

Speed governor BYC A/GAC 24V Electrical

Cooling system Forced Water Cooling Cycle

Steady speed droop (%) ≤1%

Total lubrication system capacity (L) 14.2

Coolant capacity (engine only) (L) 7.9

Fuel consumption at 100% load (g/kWh) 214 (22L/hr)

Starter motor DC24V

Alternator (Dynamo) AC24V

Alternator Specifications

Alternator model KT274C

Alternator manufacturer Kate Power copy Stamford

Exciter type Single bearing, Brushless, Self-excited

Rated output prime power 100 kVA / 80 kW

Rated speed 1500 RPM

Rated frequency 50 Hz

Phase 3

Rated voltage 400V (Available with customer requirements)

Power factor 0.8

Voltage adjust range ≥5%

Voltage regulation NL-FL ≤±1%

Insulation grade H

Protection grade IP23